 Using Twisted Wires/Solid Wires
If you use twisted wires or solid wires, use the following table to determine the correct wire specifica-
tions.
Terminals
Classifica-
tion
All terminals
except
ground
terminals
Ground
terminals
*1. Secure wires to the screwless clamping terminal block. Refer to Securing Wires on page 4-46 for how to
secure wires.
*2. With the NX-TB1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a
solid wire.
Conductor length (stripping length)
Precautions for Correct Use
• Use cables with suitable wire sizes for the carrying current. There are also restrictions on the
current due to the ambient temperature. Refer to the manuals for the cables and use the
cables correctly for the operating environment.
• For twisted wires, strip the sheath and twist the conductor portion. Do not unravel or bend the
conductor portion of twisted wires or solid wires.
Additional Information
If more than 2 A will flow on the wires, use plated wires or use ferrules.
NX-series System Units User's Manual (W523)
Current
Twisted wires
capacity
Plated
Unplated
2 A max.
Possible
Possible
Greater
than 2 A
and 4 A or
less
Greater
Not pos-
*1
Possible
than 4 A
sible
---
Possible
Possible
Unravel wires
4 Installation and Wiring
Wire type
Solid wire
Plated
Unplated
Possible
Possible
Possible
Not possi-
ble
*1
Not pos-
sible
Possible
*2
Possible
*2
Bend wires
Conductor
Wire size
length (strip-
ping length)
0.08 to 1.5
8 to 10 mm
2
mm
(AWG
28 to 16)
9 to 10 mm
2
2.0 mm
4 - 41