Quick Menu; To Enter Or Change Quick Menu Parameter Data; Example Of Changing Parameter Data - Trane TR1 6002 Installation And Operation Manual

Tr1 series. variable frequency drive
Table of Contents

Advertisement

Quick Menu

The Quick Menu gives access to the 12 most important setup
parameters of the drive. After programming the Quick Menu items, the
drive will, in many cases, be ready for operation. The Quick Menu
Quick Menu
Parameter
Item Number
Name
1
001 Language
2
102 Motor Power
3
103 Motor Voltage
4
104 Motor Frequency
5
105 Motor Current
6
106 Motor Nominal Speed
7
201 Minimum Frequency
8
202 Maximum Frequency
9
206 Ramp Up Time
10
207 Ramp Down Time
11
323 Relay 1 Function
12
326 Relay 2 Function

To Enter or Change Quick Menu Parameter Data

Enter or change parameter data or settings in accordance with the
following procedure.
1.
Press Quick Menu key.
2.
Use t and u keys to find parameter group to edit.
3.
Use ‘+’ and ‘-’ keys to find parameter you chose to edit.
4.
Press Change Data key.
5.
Use ‘+’ and ‘-’ keys to select correct parameter setting. Or, to move
to digits within a number, use t and u arrows. Flashing cursor
indicates digit selected to change.
6.
Press Cancel key to disregard change, or press OK key to accept
change and enter new setting.

Example of Changing Parameter Data

Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change
the ramp up time to 100 seconds in accordance with the following
procedure.
1.
Press Quick Menu key.
2.
Press ‘+’ key until you reach Parameter 206, Ramp Up Time.
3.
Press Change Data key.
4.
Press t key twice – hundreds digit will flash.
5.
Press ‘+’ key once to change hundreds digit from ‘0’ to ‘1.’
6.
Press u key to move cursor to tens digit.
7.
Press ‘-’ key until ‘6’ counts down to ‘0’ and setting for Ramp Up
Time reads ‘100 s.’
8.
Press OK key to enter new value into drive controller.
parameters are described in the table below. A detailed description of
the functions are given in the Programming section of this manual. The
Quick Menu is activated by pressing the QUICK MENU key on the
control panel.
Selects language used for all displays.
Sets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102, Motor Power, to convert HP to kW.
Sets output characteristics of drive based on voltage of motor.
Sets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency.
Sets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor.
Sets output characteristics of drive based on nominal full load speed of
motor.
Sets minimum controlled frequency at which motor will run.
Sets maximum controlled frequency at which motor will run.
Sets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
Sets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
Sets function of high voltage Form C relay.
Sets function of low voltage Form A relay.
Programming additional parameter functions
available through Extended Menu key is done
in accordance with same procedure as
described for Quick Menu functions.
Description
NOTE
29