Extended Menu; Manual Initialization Of Parameters; Uploading Parameters - Trane TR1 6002 Installation And Operation Manual

Tr1 series. variable frequency drive
Table of Contents

Advertisement

Extended Menu

In some applications, the Quick Menu will not access all additional
parameters necessary to set up the drive. To access all parameters,
including Quick Menu items, use the Extended Menu. The Extended
Menu is enabled by pressing the EXTEND. MENU key. The
Programming section of this manual describes in detail all the
parameters available through the Extended Menu.

Manual Initialization of Parameters

Manual initialization using either procedure
described below, or in parameter 620, will reset
the drive to standard default parameters. Any
special application programming performed at
the factory, during start-up or thereafter, will be
lost. As a backup, upload drive settings into the
driveís local control panel (LCP) keypad as
described in parameter 004, LCP Copy.
It is possible to reset parameters back to their original default values at
once. To reset the drive parameters to their read only default values, first
remove power from the drive. Then press and hold the DISPLAY
MODE, the CHANGE DATA and the OK keys down simultaneously
while reapplying power. Continue to hold down the three keys. Shortly
after power is reapplied, the bottom line of the display will read
“Initialized.” After the display stops changing, release the keys. If
“Initialized” did not appear, repeat the procedure.
These parameters are not reset by manual initialization:
Parameter 600
Operating hours
Parameter 601
Hours run
Parameter 602
kWh counter
Parameter 603
Number of power-ups
Parameter 604
Number of overtemperatures
Parameter 605
Number of overvoltages
Initialization can also be done using Parameter 620.
30
NOTE

Uploading Parameters

At any time the present parameters may be copied to the local control
panel (LCP). This may be useful when setting up multiple drives. It is
also useful when it is desired to return to a previous set of parameters.
See parameter 004, LCP Copy, for more information.
Manually initializing the drive using either the procedure described
above or parameter 620, Operating Mode, does not change the
values uploaded to the local control panel.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents