Programming Custom Display Text - Trane TR1 6002 Installation And Operation Manual

Tr1 series. variable frequency drive
Table of Contents

Advertisement

Programming Custom Display Text

Enter custom text in lines 1 (top line) or 2 (large display) of the LCP
keypad display in accordance with the following procedure.
1. Select parameter 533, Display Text Line 1 or 534, Display
Text Line 2.
2. Press CHANGE DATA key on keypad.
3. Use left or right arrows on keypad to position cursor.
4. Use [+] or [-] arrows to scroll through character options.
5. Press [OK] key to accept changes or [CANCEL] key to
cancel.
6. Select Free Program Array in parameter 007, Large read-
out, to activate custom text readout.
NORTH OFFICE BLDG
Pump 6
AUTO REMOTE RUN
The available characters are:
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Æ Ø Å Ä Ö Ü
É Ì Ù è . / - ( ) 0 1 2 3 4 5 6 7 8 9 “space”
To erase a character that has been entered, replace it with “space.”
535
Bus Feedback 1
(BUS FEEDBACK1)
Value:
0 through 16384 decimal (0 through 4000 Hex)
Function:
Via the serial communication port, this parameter allows writing of a bus
feedback value which will then form part of the feedback handling. Bus
Feedback 1 will be added to any feedback value registered on terminal
53.
Description of choice:
Write the required bus feedback value via serial communication.
536
Bus Feedback 2
(BUS FEEDBACK 2)
Value:
0 through 16384 decimal (0 through 4000 Hex)
Function:
Via serial communication, a bus feedback value can be written in this
parameter that will become part of the feedback handling system. Bus
Feedback 2 will be added to any feedback value on terminal 54.
Description of choice:
Write the required bus feedback value via the serial communication.
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
80
SETUP
1
★ 0
★ 0
537
Relay Status
(RELAY STATUS)
Value:
binary (0 = open, 1 = closed)
Description of choice:
See Data Read-out for parameters 509 through 532, 537 on previous
page for relay status description.
Parameters 555, Bus Time Interval, and 556, Bus
Time Interval Function, are only active when
FC Protocol has been selected in parameter
500, Protocol.
555
Bus Time Interval
(BUS TIME INTERVAL)
Value:
1 to 99 sec.
Function:
In this parameter, the maximum time allowed between the receipt of two
packets in a row is set. If this time is exceeded, the serial communication
is assumed to have stopped and the choice made in parameter 556,
Bus Time Interval Function, will be carried out.
Description of choice:
Set the required time.
556
Bus Time Interval Function
(BUS TIME INTERVAL FUNCTION)
Value:
★ Off (NO FUNCTION)
Freeze output (FREEZE OUTPUT)
Stop (STOP)
Jogging (JOG FREQUENCY)
Max. output frequency (MAX FREQUENCY)
Stop and trip (STOP AND TRIP)
Function:
In this parameter, the required reaction from the drive is selected when
the time set in parameter 555, Bus Time Interval, has been exceeded.
Description of choice:
The output frequency of the drive can be frozen at the present value,
frozen as selected in parameter 211, Preset Reference 1, frozen as
selected in parameter 202, Maximum Output Frequency, or stop and
show a fault.
★ 0
NOTE
★ 60 sec.
[0]
[1]
[2]
[3]
[4]
[5]