Relay Card Functions Parameters 700 Through 711; Electrical Installation Of The Relay Card - Trane TR1 6002 Installation And Operation Manual

Tr1 series. variable frequency drive
Table of Contents

Advertisement

Relay Card Functions
Parameters 700 through 711
Parameters 700 through 711 are only activated if a relay option card is
installed in the drive. A relay card can be field installed in the drive if
desired.
Activation/deactivation can be programmed in parameters 701, 704,
707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702,
705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
700
Relay 6, Function
703
Relay 7, Function
706
Relay 8, Function
709
Relay 9, Function
Function:
This output activates a relay.
Relay outputs 6, 7, 8 and 9 can be used for showing status and
warnings. The relay is activated when the conditions for the relevant
data values have been fulfilled. Because these have the same possible
functions as relay 1, see the description under parameter 323.
701
Relay 6, ON Delay
704
Relay 7, ON Delay
707
Relay 8, ON Delay
710
Relay 9, ON Delay
Value:
0 to 600 sec.
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
Description of choice:
Enter the desired value.
702
Relay 6, OFF Delay
705
Relay 7, OFF Delay
708
Relay 8, OFF Delay
711
Relay 9, OFF Delay
Value:
0 to 600 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8
and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value.
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
✭ I
ndicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.
(RELAY6 FUNCTION)
(RELAY7 FUNCTION)
(RELAY8 FUNCTION)
(RELAY9 FUNCTION)
(RELAY6 ON DELAY)
(RELAY7 ON DELAY)
(RELAY8 ON DELAY)
(RELAY9 ON DELAY)
★ 0 sec.
(RELAY6 OFF DELAY)
(RELAY7 OFF DELAY)
(RELAY8 OFF DELAY)
(RELAY9 OFF DELAY)
★ 0 sec.

Electrical Installation of the Relay Card

The relays are connected as shown below.
Relay 6-9
A-B make, A-C break
Max. 240 VAC, 2 Amp
To achieve double isolation, mount the plastic foil as shown below.
93