Internal Drive Fuses

The table below specifies fuses used internally in the TR1 series
drives. Use the specified fuse or an exact replacement only.
Internal Fuses Provided with TR1 Series VFDs
200 – 240 VAC
TR1 Type
Soft Charge Fuse
(3X)
6042
Littelfuse KLK-15
Littelfuse KLK-D-12
6052
Littelfuse KLK-15
Littelfuse KLK-D-12
6062
Littelfuse KLK-15
Littelfuse KLK-D-12
380 – 460 VAC
TR1 Type
Soft Charge
Fuse (3X)
6072
Littelfuse KLK-15
Littelfuse KLK-D-12 (1X)
6102
Littelfuse KLK-15
Littelfuse KLK-D-12 (1X)
6122
Littelfuse KLK-15
Littelfuse KLK-D-12 (1X)
6150
Littelfuse KLK-30
Littelfuse KLK-D-12 (1X)
6175
Littelfuse KLK-30
Littelfuse KLK-D-12 (2X)
6225
Littelfuse KLK-30
Littelfuse KLK-D-12 (2X)
6275
Littelfuse KLK-30
Littelfuse KLK-D-12 (2X)
TR1 Type
Soft Charge
Fuse (3X)
6350
Littelfuse KLK-9
Littelfuse KLK-15
6400
Littelfuse KLK-9
Littelfuse KLK-15
6500
Littelfuse KLK-9
Littelfuse KLK-15
6550
Littelfuse KLK-9
Littelfuse KLK-15
TR1 Type
Soft Charge
Fuse (3 phase)
6152
Bussmann
FWH20A6F
6172
Bussmann
FWH20A6F
6222
Bussmann
FWH20A6F
6272
Bussmann
FWH20A6F
6352
Bussmann
FWH20A6F
Soft Charge Resistor
Power Card
Fuse (1X)
Fuse (1X)
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Soft Charge Resistor
Power Card
Fuse (1X or 2X)
Fuse (1X)
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Line Snubber
Interface Board
Fuse (3X)
Fuse (1X)
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Bussmann KTK-5
Fan Fuse
Power Card/SMPS
(1 phase)
Fuse (1 phase)
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4
Bussmann KTK-4

Terminal Identification

The connectors for input and output power, auxiliary relay connections,
and external DC bus are identified in the tables below.
L1
AC Line
91
U
Motor
96
AUX RELAY
01
(-) DC
DC Bus
88
CAUTION
Drive Failure!
Do not connect input power to drive output
motor terminals. Connecting input power to
motor terminals will result in drive failure when
power is applied.
On drives with an auxiliary enclosure, some or all of the power
connections at the drive will be factory made. Custom input and output
terminals may be inside the auxiliary enclosure. See the drawings
supplied with the drive for details on custom terminal blocks and conduit
entry locations for the auxiliary enclosure.

Input Power Delay

To ensure that the input surge suppression circuitry performs correctly,
a time delay between successive applications of input power must be
observed.
The table below shows the minimum time that must be allowed between
applications of input power.
Input voltage
380 V
W aiting time
48 sec
L2
L3
92
93
V
W
PE (ground)
97
98
99
02
03
(+) DC
89
415 V
460 V
600 V
65 sec
89 sec
133 sec
11