Typical Control Connections - Trane TR1 6002 Installation And Operation Manual

Tr1 series. variable frequency drive
Table of Contents

Advertisement

Typical Control Connections

Shown below are typical interfaces between the TR1 and other
components in an HVAC system. The terminal numbers and the
functions of the terminals are identical on all TR1s. An optional relay
card, not shown, can provide four additional Form C output relays.
The RS-485 connections allow direct communication through the
drive’s built-in serial communication protocols.
3 Phase
Power
Input
External
DC Bus
Connection
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
Preset Speed*
Setup Select*
Setup Select*
Typical TR1 Wiring
91 (L1)
92 (L2)
93 (L3)
99 (PE)
88 (-)
89 (+)
10 V DC
17 mA
+
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
60 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
SW4
27 (D IN)
29 (D IN)
32 (D IN)
33 (D IN)
* The operation of all control inputs and outputs is programmable.
*
Typical terminal functions are shown.
Switch Mode
Power Supply
24 V DC
200 mA
-
+
-
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
(RELAY) 04
(RELAY) 05
(COM A OUT) 39
5 V
(A OUT) 42
0 V
SW2
SW3
(A OUT) 45
EIA-485
(P EIA-485) 68
Interface
(N EIA-485) 69
(COM EIA-485) 61
(U) 96
(V) 97
(W) 98
Motor
(PE) 95
Fault Indication*
240 V AC, 2 A
Run Indication*
30 V AC, 1 A
Output Current Indication*
4 - 20 mA
Output Speed Indication*
4 - 20 mA
+
EIA-485
-
21