Input Fuses

CAUTION
Branch Circuit Fuses Required!
All drives must be protected with branch circuit
fuses in accordance with the National Electrical
Code. Failure to provide branch circuit fuses in
accordance with the NEC may result in
equipment or property damage.
To comply with UL508C, input fuses shown in the tables below must be
installed in the power supply to drives which are 208 V above 30 hp,
and 380/460 V and 600 V drives above 75 hp. The fuse ratings in the
tables below are the recommended maximum ratings.
Any UL listed Class T fuse with equivalent
voltage and current rating may be used in place
of JJS and JJN fuse types.
Trane recommends input fuses on all drives. If specified as a drive
option, input fuses will be installed by The Trane Company in an
enclosure external to the drive, which may include other optional
features. If not supplied, they must be provided by the drive installer as
part of installation.
380/460 Volt Input
Maximum Fuse
TR1 Type
Rating (Amps)
6002
10
6003
15
6004
15
6006
25
6008
35
6011
45
6016
70
6022
90
6027
110
6032
125
6042
175
6052
200
6062
200
6072
250
6102
300
6122
350
6150
300
6152
300
6172
300
6175
350
6222
350
6225
400
6272
400
6275
500
6350
600
6352
600
6400
700
6500
800
6550
800
10
NOTE
Bussmann Type
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
FWH
208/230 Volt Input
Ma x im um Fuse
TR1 Type
Ra ting (Am ps)
6002
20
6003
20
6004
40
6006
50
6008
80
6011
100
6016
150
6022
200
6027
225
6032
300
6042
400
6052
200
6062
250
600 Volt Input
Maximum Fuse
TR1 Type
Rating (Amps)
6002
10
6003
10
6004
15
6006
20
6008
25
6011
35
6016
50
6022
60
6027
80
6032
90
6042
110
6052
150
6062
175
6072
100
6100
125
6125
175
6150
200
6175
250
6225
350
6275
400
200-240 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 250 V maximum.
380-460 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 500 V maximum.
550-600 V drives are suitable for use on a circuit capable of supplying a
maximum of 100,000 A RMS (symmetrical), 600 V maximum.
Bussma nn Type
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
JJN or JJS
FW X or FW H
FW X or FW H
Bussmann Type
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
JJS
FWP
FWP
FWP
FWP
FWP
FWP

Hide quick links: