List of Settings

The following are the setting descriptions, setting ranges, and default values of the functions that can
be used in the Digital Mixed I/O Units.
The settings are reflected after the Unit is restarted.
Precautions for Safe Use
The Unit is required to restart after the transfer of Unit operation settings on the Support Soft-
ware is completed. Always sufficiently check the safety at the connected devices before you
transfer the Unit operation settings.
8-3-1

Input Settings

This section describes the allocable I/O data in the Digital Mixed I/O Units.
NX Units in Free-Run Refreshing or Synchronous I/O Refreshing
Sixteen-point Input Units
Setting name
Input Filter Value Setting
Input Filter Mode Setting
*1. The descriptions of Input Filter Value Setting are as follows.
Set
value
0
1
2
3
4
5
6
7
8
9
10
11
NX-series Digital I/O Unit User's Manual (W521)
Description
Set the filter time of input
*1
signal.
Set the operating mode
*2
for the filter.
Setting description
No Filter
0.25 ms
0.5 ms
1 ms
2 ms
4 ms
8 ms
16 ms
32 ms
64 ms
128 ms
256 ms
8 Digital Mixed I/O Units
Default
Setting
Unit
value
range
---
*1
*1
---
*2
*2
Default value
3
Subin-
Refer-
Index
dex
ence
5000
01 hex
P. 6-14
hex
02 hex
P. 6-14
Setting range
0 to 11
8 - 5
8