Omron NX-ID User Manual page 283

Machine automation controller nx-series digital i/o units
Table of Contents

Advertisement

DC Input Units (Fujitsu Connector, 30 mm Width)
Unit name
DC Input Unit
Number of points
32 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, input indicators
Dimensions
30 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from external source
method
NX Unit power con-
• Connected to a CPU Unit
sumption
0.95 W max.
• Connected to a Communications Cou-
pler Unit
0.55 W max.
Weight
90 g max.
Circuit layout
Connector
NX bus
connector
(left)
NX-series Digital I/O Unit User's Manual (W521)
Model
External connection
terminals
Internal I/O common
Rated input voltage
Input current
ON voltage/ON current
OFF voltage/OFF cur-
rent
ON/OFF response time
Input filter time
Isolation method
Dielectric strength
Current capacity of I/O
power supply terminal
Current consumption
from I/O power supply
Input indicator
3.3 kΩ
IN0
to
IN15
COM0
COM0
3.3 kΩ
IN16
to
IN31
COM1
COM1
I/O power
supply +
I/O power
supply −
Appendices
NX-ID6142-6
Fujitsu connector (40 terminals)
For both NPN/PNP
24 VDC (19 to 28.8 VDC)
4.1 mA typical (24 VDC)
19 VDC min./3 mA min. (between COM
and each signal)
5 VDC max./1 mA max. (between COM
and each signal)
20 μs max./400 μs max.
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2
ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128
ms, 256 ms
Photocoupler isolation
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Without I/O power supply terminals
No consumption
I/O power
NX bus
supply +
connector
I/O power
(right)
supply −
A