Omron NX-ID User Manual page 310

Machine automation controller nx-series digital i/o units
Table of Contents

Advertisement

Appendices
Unit name
Transistor Output Unit
Number of points
16 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, output indicator
Dimensions
12 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from the NX bus
method
NX Unit power con-
• Connected to a CPU Unit
sumption
1.10 W max.
• Connected to a Communications Cou-
pler Unit
0.70 W max.
Weight
70 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation:
tion and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
A - 60
I/O power supply +
I/O power supply −
Model
NX-OD5256
External connection
Screwless clamping terminal block (16 ter-
terminals
minals)
Internal I/O common
PNP
Rated voltage
24 VDC
Operating load voltage
15 to 28.8 VDC
range
Maximum value of load
0.5 A/point, 4 A/Unit
current
Maximum inrush cur-
4.0 A/point, 10 ms max.
rent
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON/OFF response time
0.5 ms max./1.0 ms max.
Isolation method
Photocoupler isolation
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Current capacity of I/O
Without I/O power supply terminals
power supply terminal
Current consumption
40 mA max.
from I/O power supply
NX-series Digital I/O Unit User's Manual (W521)
OUT0 to OUT15 Terminal block
I/O power supply +
NX bus
connector
I/O power supply −
(right)