Omron NX-ID User Manual page 281

Machine automation controller nx-series digital i/o units
Table of Contents

Advertisement

Installation orienta-
Installation orientation:
tion and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: As shown in the following.
• For upright installation
• For any installation other than upright
NX-series Digital I/O Unit User's Manual (W521)
Number of simultaneously ON input points vs.
Ambient temperature characteristic
35
30
32 points at 40°C
25
20
15
I/O power supply voltage
10
24 V
5
28.8 V
0
0
10
20
30
Ambient temperature
Number of simultaneously ON input points vs.
Ambient temperature characteristic
35
30
32 points at 30°C
25
20
15
I/O power supply voltage
10
19 V
5
24 V
28.8 V
0
0
10
20
30
Ambient temperature
32 points at 45°C
13 points/common at 55°C
10 points/common at 55°C
40
45
50
55
60
(°C)
32 points at 35°C
32 points at 50°C
13 points/common at 55°C
8 points/common at 55°C
5 points/common at 55°C
40
45
50
55
60
(°C)
Appendices
A
A - 31

Advertisement

Table of Contents
loading

Table of Contents