Installation orientation
Installation orientation:
and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: As shown in the following.
• For upright installation
• For any installation other than upright
A - 86
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 35°C
16
12
8
I/O power supply voltage
24 V
4
28.8 V
0
0
10
20
30
Ambient temperature
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 25°C
16
12
I/O power supply
8
voltage
24 V
4
28.8 V
0
0
10
20
30
Ambient temperature
16 points at 45°C
13 points at 55°C
9 points at 55°C
40
45
50
55
60
(°C)
16 points at 40°C
5 points at 55°C
3 points at 55°C
40
45
50
55
60
(°C)