Unit name
DC Input Unit
Number of points
4 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, input indicators
Dimensions
12 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from the NX bus
method
NX Unit power con-
• Connected to a CPU Unit
sumption
0.90 W max.
• Connected to a Communications Cou-
pler Unit
0.50 W max.
Weight
65 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation:
tion and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
Terminal connection
diagram
12 to 24 VDC
A - 14
IOV0 to 3
IN0 to IN3
Terminal block
IOG0 to 3
I/O power supply +
I/O power supply −
Additional I/O
Power Supply Unit
A1
B1
IOV
IOV
IOG
IOG
IOV
IOV
IOG
IOG
A8
B8
Model
External connection
terminals
Internal I/O common
Rated input voltage
Input current
ON voltage/ON current
OFF voltage/OFF cur-
rent
ON/OFF response time
Input filter time
Isolation method
Dielectric strength
Current capacity of I/O
power supply terminal
Current consumption
from I/O power supply
Current control
circuit
DC Input Unit
NX-ID3417
Two-wire
sensor
A1
B1
IN0
IN1
IOV0
IOV1
IOG0
IOG1
IN2
IN3
IOV2
IOV3
IOG2
IOG3
A8
B8
NX-series Digital I/O Unit User's Manual (W521)
NX-ID3417
Screwless clamping terminal block (12 ter-
minals)
PNP
12 to 24 VDC (9 to 28.8 VDC)
6 mA typical (at 24 VDC), rated current
9 VDC min./3 mA min. (between IOG and
each signal)
2 VDC max./1 mA max. (between IOG and
each signal)
20 μs max./400 μs max.
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2
ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128
ms, 256 ms
Photocoupler isolation
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
:
:
IOV
0.1 A/terminal max., IOG
0.1 A/termi-
nal max.
No consumption
I/O power supply +
NX bus
connector
I/O power supply −
(right)
Three-wire