Unit name
Transistor Output Unit
Number of points
16 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, output indicator
Dimensions
30 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supplied from external source.
method
NX Unit power con-
• Connected to a CPU Unit
sumption
1.00 W max.
• Connected to a Communications Cou-
pler Unit
0.70 W max.
Weight
85 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation:
tion and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
A - 68
Model
External connection
terminals
Internal I/O common
Rated voltage
Operating load voltage
range
Maximum value of load
current
Maximum inrush cur-
rent
Leakage current
Residual voltage
ON/OFF response time
Isolation method
Dielectric strength
Current capacity of I/O
power supply terminal
Current consumption
from I/O power supply
I/O power
supply +
I/O power
supply −
NX-OD5256-5
MIL connector (20 terminals)
PNP
24 VDC
20.4 to 28.8 VDC
0.5 A/point, 2 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max./1.0 ms max.
Photocoupler isolation
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Without I/O power supply terminals
40 mA max.
COM (+V)
COM (+V)
OUT0 to OUT15
0V
0V
I/O power
NX bus
supply +
connector
I/O power
(right)
supply −
NX-series Digital I/O Unit User's Manual (W521)