LOGO! installation and wiring
CM EIB/KNX, behaviour on communication failure
S
LOGO! voltage failure
If there is a power failure of the LOGO! or a disruption in
the communication to the LOGO! master or to the
communication partner on the left-hand side, the
outputs are set to 0. The RUN/STOP LED lights up red
after a second.
S
LOGO! voltage recovery
LOGO! starts up again, CM EIB/KNX sends the
parameterised states.
S
CM EIB/KNX voltage failure
All the inputs of the LOGO! master on the EIB are set to
0 by the LOGO! master.
S
CM EIB/KNX voltage recovery
All the outputs of the LOGO! master on the EIB are
updated. The inputs are read by the EIB depending on
the parameterisation.
S
Short circuit on the bus or bus interruption
The behaviour can be parameterised in the LOGO!
configuration window of the application program in ETS
(EIB Tool Software). After 5 s, the red LED is set.
S
Bus recovery
The behaviour can be parameterised in the LOGO!
configuration window.
52
LOGO! Manual
A5E00380835-01