A.12 Technical Data: Logo! Am 2 Aq - Siemens Logo! Manual

Hide thumbs Also See for Logo!:
Table of Contents

Advertisement

A.12 Technical data: LOGO! AM 2 AQ

Power supply
Input voltage
Permissible range
Power consumption
Voltage failure buffering
Power loss
Electrical isolation
Reverse polarity protection
Ground terminal
Analog outputs
Number
Output range
Maximum load
Resolution
Cycle time for analog output
Electrical isolation
Line length (shielded and
twisted)
Error limit
LOGO! Manual
A5E00380835-01
LOGO! AM 2 AQ
24 V DC
20.4 ... 28.8 V DC
25 ... 50 mA
typ. 5 ms
0.6 ... 1.2 W
No
Yes
for connecting ground and shielding of
the analog output line.
2
0 ... 10 V DC
5 kW
10 bit, normalized to 0 ... 1000
depending on installation (50 ms)
No
10 m
+/– 2.5 % FS