LOGO! functions

4.4.27 Analog Ramp

Short description
This special function starts up at the analog output 0 or one
of 2 levels. Here you can set how quickly the level should
be reached.
Symbol in
LOGO!
220
Wiring
Input En
Input Sel
Input St
Description
A change in the status from
0 to 1 at input En (Enable)
launches the start-up of a
parameterized analog value
at output AQ.
A change in status from 1 to
0 immediately issues 0 at
output AQ.
S
SeI = 0:
Level 1 is started
S
SeI = 1:
Level 2 is started
A change in the status from
0 to 1 at input En (Enable)
launches the start-up of the
value 0 at output AQ.