Note
To disable summertime/wintertime conversion in this
menu, you merely confirm 'Off' with OK.
Note
Summertime/wintertime conversion only functions when
LOGO! is operating (in RUN or STOP status). It does not
function when LOGO! is in buffered operation (see Chapter
4.3.3).

3.7.14 Synchronization

Time synchronization between LOGO! and a connected
communication module EIB/KNX (version 0AA1 upwards!)
can be enabled/disabled
S
in parameter assignment mode by means of the set
menu ("Clock" menu item)
S
in programming mode by means of the setup menu
("Clock" menu item).
Note
When using a LOGO! basic module with digital or analog
expansion modules, but without communication module
EIB/KNX (version 0AA1 upwards), time synchronization
must not be activated! You must check whether time syn-
chronization is deactivated ('Sync' must be set to 'Off').