4-4-2
Precautions when Wiring to the Output Units
Output Short-circuit Protection
If a load connected to the output terminals is short-circuited, output components and printed circuit
boards may be damaged. To guard against this, use the NX Units with load short-circuit protection.
When using the NX Units without load short-circuit protection, incorporate a protective fuse in the exter-
nal circuit. Use a fuse with a capacity of around twice the rated output.
Inrush Current
When connecting a transistor to an output device with a high inrush current (such as an incandescent
lamp), steps must be taken to avoid damage to the output transistor.
Use either of the following methods to reduce the inrush current.
Countermeasure 1
Draw about 1/3 of the current consumed by the load.
When I/O power is supplied from the NX bus, the method is as shown in the following figure.