4 Installation and Wiring
 Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, the applicable wire range and conductor length (strip-
ping length) are as follows.
Terminal types
Ground terminals
Terminals other than
ground terminals
*1. When you use the NX-TB1 Terminal Block, use twisted wires to connect the ground terminal. Do
not use solid wires.
Conductor length (stripping length)
Precautions for Correct Use
• Use cables with suitable wire sizes for the carrying current. There are also restrictions on the
current due to the ambient temperature. Refer to the manuals for the cables and use the
cables correctly for the operating environment.
• For twisted wires, strip the sheath and twist the conductor portion. Do not unravel or bend the
conductor portion of twisted wires or solid wires.
4 - 18
Applicable wire range
*1
2
2.0 mm
0.08 to 1.5 mm
AWG28 to 16
Unravel wires
Conductor length (stripping length)
9 to 10 mm
8 to 10 mm
2
Bend wires
NX-series Digital I/O Unit User's Manual (W521)