5001
Input Filter Setting
00
Number of Entries
01
Input Filter Value Setting
02
Input Filter Mode Setting
*1. The default value and data range for Number of Entries are as follows.
NX Units
NX-ID3343/ID3443
Other models
*2. The meaning of the set values for Input Filter Value Setting is as follows.
Set value
0
No Filter
1
1 μs
2
2 μs
3
4 μs
4
8 μs
5
16 μs
6
32 μs
7
64 μs
8
128 μs
9
256 μs
*3. The meaning of the set values for Input Filter Mode Setting is as follows.
Set value
0
Enable ON Filter and OFF Filter
1
Enable Only OFF Filter
NX-series Digital I/O Unit User's Manual (W521)
Default
Object name
value
*1
4
0
Default value
2
0
Meaning
Meaning
Data
Data range
Unit
type
USINT
*1
USINT
*2
0 to 9
USINT
*3
0/1
Data range
2 (fixed)
0 (fixed)
Appendices
I/O
Data
Acc
allo-
attri-
ess
cat-
bute
ion
RO
Not
pos-
sible
RW
Not
Y
pos-
sible
RW
Not
Y
A
pos-
sible
A - 87