Omron NX-ID3343 User Manual page 267

Nx-series digital i/o units machine automation controller
Table of Contents

Advertisement

Unit name
Transistor Output Unit
Number of points
16 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, output indicator
Dimensions
12 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from the NX bus
method
NX Unit power con-
0.70 W max.
sumption
Weight
70 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation: Possible in 6 orientations.
tion and restrictions
Restrictions: No restrictions
Terminal connection
diagram
24 VDC
Disconnec-
Not supported.
tion/Short-circuit
detection
NX-series Digital I/O Unit User's Manual (W521)
I/O power supply +
I/O power supply −
Additional I/O
I/O Power Supply
Power Supply Unit
Connection Unit
A1
B1
A1
IOV
IOV
IOV
IOV
IOV
IOV
IOG
IOG
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOG
IOG
IOV
IOV
IOV
IOV
A8
B8
A8
Model
NX-OD5256
External connection
Screwless clamping terminal block (16 ter-
terminals
minals)
Internal I/O common
PNP
Rated voltage
24 VDC
Operating load voltage
15 to 28.8 VDC
range
Maximum value of load
0.5 A/point, 4 A/NX Unit
current
Maximum inrush cur-
4.0 A/point, 10 ms max.
rent
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON/OFF response time
0.5 ms max./1.0 ms max.
Isolation method
Photocoupler isolation
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Current capacity of I/O
Without I/O power supply terminals
power supply terminal
Current consumption
40 mA max.
from I/O power supply
I/O Power Supply
Transistor Output
Connection Unit
Unit
NX-OD5256
B1
A1
B1
A1
OUT0
OUT1
IOG
IOG
OUT3
OUT2
IOG
IOG
IOG
IOG
OUT4
OUT5
IOG
IOG
OUT6
OUT7
IOG
IOG
OUT8
OUT9
IOG
IOG
OUT10
OUT11
OUT12
OUT13
IOG
IOG
IOG
OUT14
OUT15
IOG
B8
A8
B8
A8
Protective function
With load short-circuit protection.
Appendices
OUT0 to OUT15 Terminal block
I/O power supply +
NX bus
connector
I/O power supply −
(right)
Two-wire type
B1
Three-wire type
B8
A - 37
A

Hide quick links: