Omron NX-ID3343 User Manual page 216

Nx-series digital i/o units machine automation controller
Table of Contents

Advertisement

9 Troubleshooting
Event name
NX Unit I/O Communications Error
Meaning
An I/O communications error occurred between the Communications Coupler Unit and the NX Unit.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The NX Unit is not mounted prop-
erly.
The power cable for the Unit
power supply is disconnected. Or,
the wiring from the Unit power
supply to the NX Units is incorrect.
The power cable for the Unit
power supply is broken.
The voltage of the Unit power sup-
ply is outside the specified range.
Or, the capacity of the Unit power
supply is insufficient.
There is a hardware error in the
NX Unit.
Attached
None
information
Precautions/
None
Remarks
9 - 12
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Correctly wire the Unit power sup-
ply to the NX Units.
Replace the power cable between
the Unit power supply and the NX
Units.
Correctly configure the power sup-
ply system according to the power
supply design methods.
If the error occurs again even after
you make the above correction,
replace the NX Unit.
Event code
80200000 hex
NX Unit
Detection
timing
When the
Log category
fail-soft opera-
tion for the
Communica-
tions Coupler
Unit is set to
stop, reset all
errors in Con-
troller.
When the
fail-soft opera-
tion for the
Communica-
tions Coupler
Unit is set to
fail-soft, reset
errors in Com-
munications
Coupler Unit
and NX Unit.
The NX Unit will continue to operate.
Input data: Updating input values stops.
Output data: The output values depend on the Load
Rejection Output Setting.
Name
---
Prevention
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Correctly wire the Unit power sup-
ply to the NX Units.
None
Correctly configure the power sup-
ply system according to the power
supply design methods.
None
NX-series Digital I/O Unit User's Manual (W521)