Event name
NX Unit Output Synchronization Error
Meaning
An output synchronization error occurred in the NX Unit.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The NX Unit is not mounted prop-
erly.
The Slave Terminal Configuration
Information when the EtherCAT
Coupler Unit synchronization set-
tings were downloaded did not
agree with the actual configuration
of the Slave Terminal.
There is an NX Unit that cannot be
synchronized to the specified out-
put synchronization timing.
(This will not cause an error when
the synchronization setting is
made from the Sysmac Studio.)
Attached
None
information
Precautions/
None
Remarks
NX-series Digital I/O Unit User's Manual (W521)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Correct the actual configuration of
the Slave Terminal so that it
agrees with the Slave Terminal
Configuration Information when
the EtherCAT Coupler Unit
synchronization settings are
downloaded. Or, download
synchronization settings that
agree with the actual configuration
of the Slave Terminal.
Adjust the timing of output
synchronization to the slowest NX
Unit of the NX Units to
synchronize.
9 Troubleshooting
Event code
80210000 hex
NX Unit
Detection
timing
Reset all errors
Log category
in Controller.
The NX Unit will continue to operate.
Input data: Updating input values stops.
Output data: The output values depend on the Load
Rejection Output Setting.
Name
---
Prevention
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Correct the actual configuration of
the Slave Terminal so that it
agrees with the Slave Terminal
Configuration Information when
the EtherCAT Coupler Unit syn-
chronization settings are down-
loaded. Or, download
synchronization settings that
agree with the actual configuration
of the Slave Terminal.
Adjust the timing of output syn-
chronization to the slowest NX
Unit of the NX Units to synchro-
nize.