Appendices
Transistor Output Units (MIL Connector, 30 mm Width)
Unit name
Transistor Output Unit
Number of points
16 points
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator, output indicator
Dimensions
30 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from external source
method
NX Unit power con-
0.60 W max.
sumption
Weight
80 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation: Possible in 6 orientations.
tion and restrictions
Restrictions: No restrictions
Terminal connection
diagram
12 to
24 VDC
• Be sure to wire both pins 3 and 4 (COM).
• Be sure to wire both pins 1 and 2 (+V).
A - 38
I/O power
supply +
I/O power
supply −
Signal
Connector
Signal
name
pin
name
+V
+V
1
2
COM
COM
3
4
OUT15
OUT07
5
6
L
OUT14
OUT06
7
8
L
OUT13
OUT05
9
10
L
OUT12
OUT04
11
12
L
OUT11
OUT03
13
14
L
OUT10
OUT02
15
16
L
OUT09
OUT01
17
18
L
OUT08
OUT00
19
20
L
Model
NX-OD5121-5
External connection
MIL connector (20 terminals)
terminals
Internal I/O common
NPN
Rated voltage
12 to 24 VDC
Operating load voltage
10.2 to 28.8 VDC
range
Maximum value of load
0.5 A/point, 2 A/NX Unit
current
Maximum inrush cur-
4.0 A/point, 10 ms max.
rent
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON/OFF response time
0.1 ms max./0.8 ms max.
Isolation method
Photocoupler isolation
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Current capacity of I/O
Without I/O power supply terminals
power supply terminal
Current consumption
30 mA max.
from I/O power supply
+V
+V
OUT0 to OUT15
COM
COM
I/O power
supply +
I/O power
supply −
L
L
L
L
L
L
L
L
NX-series Digital I/O Unit User's Manual (W521)
Connector
NX bus
connector
(right)