UPS system. The module uses an RS422 serial interface line and may support up
to eight critical loads. A maximum of two monitoring accessories (RMPs, RIMs, or
SCMs) can be installed. Refer to Chapter 10, Table D for the number of
accessories permitted. Figure 23 shows the RIM with its four 15-pin connectors
labeled J1 through J4. Drawing 164200292---11 in Appendix A outlines the
enclosure dimensions.
15-PIN D-SUB
CONNECTORS
To install an RIM:
1.
Securely mount the RIM.
2.
Install wiring from the RIM using ½-in. conduit through the
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3.
If not already installed, locate the RMP adapter cable assembly (see Figure 24)
in the spare parts kit. Mate the DE---9 connector on the back of the terminal
block into the DE---9 connector on the Communications Panel of the UPS (see
Figure 25). Use two screws from the spare parts kit to secure the terminal
block bracket to the Communications Panel.
Powerware 9315 (100 kVA- -160 kVA) Installation
164200292 Rev. E 041500
Installing a Relay Interface Module
The optional Relay Interface Module (RIM) uses relay contact
closures to indicate the operating status and alarm condition of the
Relay Interface Module
J1
J2
J3

Figure 23. Relay Interface Module

FLUSH MOUNT
SURFACE
MOUNT
FOR HANGING
J4
CONTINUES
AT UPS
in. knockout in
7/8-
45