FP2/FP2SH
2.9.2

32-point Type DC Input Unit

Specifications
Item
Part number
Insulation method
Rated input voltage
Rated input current
Input impedance
Input voltage range
Min. on voltage/Min. on current
Max. off voltage/Max. off current
Response time
p
Internal current consumption (at 5V DC)
Common method (Input points per common) 32 points/common
Operating indicator
External connection method
Weight
Internal Circuit Diagram
Input
5.6kΩ
24V DC
COM
Description
FP2−X32D2
Optical coupler
24V DC
Approx. 4.3mA (at 24V DC)
Approx. 5.6kΩ
20.4 to 26.4V DC
19.2V/4mA
5.0V/1.5mA
off → on
0.2ms or less
on → off
0.3ms or less
80mA or less
Either the positive or negative of the input power supply can be
connected to common terminal.
32-dot LED display (lit when on)
Connectors (MIL type 40-pin)
Approx. 100g
Input indicator LED
560Ω