Panasonic fp2/fp2sh User Manual page 69

Programmable controller
Table of Contents

Advertisement

FP2/FP2SH
Specifications
Item
Part number
Size of unit
Input
p
Rated voltage
Current consumption
Surge current
Rated frequency
Operating voltage
range
Output
Output capacity at 5V
Alarm contact capacity
Alarm contact operation
Alarm contact type
Leakage current
Breakdown voltage
Insulation resistance
Guaranteed lifetime
Overcurrent protection function
Fuse
Terminal screw
*1 The allowable variation in voltage after startup is 15.6V to 31.2V.
Description
FP2−PSA1
FP2−PSA2
1−module
100 to 120V AC
200 to 240V AC
0.4A or less
0.2A or less
(at 100V AC)
(at 200V AC)
40A or less
50Hz/60Hz
85 to 132V AC
170 to 264V AC
Max. 2.5A
30V DC 1A
When the ALARM LED of CPU is lit
1c contact
Between input and ground terminals, 0.75mA or less
1500V AC for 1 minutes
(between input and ground terminals)
100MΩ 500V DC (between input and ground terminals)
20000 hours at 55°C/131°F
Built-in overcurrent protection
Built-in
M3
Parts and Functions
2.7
Power Supply Units
FP2−PSA3
FP2−PSD2
2−module
100 to 240V AC
24V DC
0.7A or less
2.5A or less
(at 100V AC)
0.4A or less
(at 200V AC)
30A or less
10A or less
(at 25°C/77°F)
85 to 264V AC
20.4 to 31.2V DC
(*1)
Max. 5A
Max. 5A
500V AC for 1
minutes (between
input and ground
terminals)
2 − 29

Advertisement

Table of Contents
loading