OM-2226 / Operation and Maintenance Manual
60CU20 / Series 500062 / 400 Hz. Generator Set
Water Drain
e
Check Fault Code Meter
At each daily start-up, observe the fault code meter on the control panel. If the display shows
"air", change the air filter. See Section 2-4 for other fault codes.
f

Check Exhaust System

Visually inspect muffler and exhaust pipes for rust and signs of approaching failure. Listen for
any gasket or joint leaks.
WARNING
A leaking and defective exhaust system could be a fire hazard.
(2) Electrical System (12 VDC)
a
Check All Lights
Check all indicating lights to be sure they will operate when they should. If any light fails to
operate, check both the lamp and its protective circuit breaker. Figure 5 lists all lamps with
their location and part number. Figure 6 lists all circuit breakers.
b
Check Engine Battery Voltage
Observe the 12 VDC engine voltmeter each time the engine is started to be sure the
alternator is functioning correctly and charging the batteries. If the batteries need to be
replaced, be sure the replacements meet the specifications for Cold Cranking Amps (CCA)
and Reserve Capacity.
c
Check the operation of all the engine meters.
May 2, 2013
Fuel Pre-Filter and Drain
Figure 2
Chapter 2-1
Page 6