Exciter Armature - Hobart 60CU20 Operation And Maintenance Manual With Illustrated Parts List

60 kva, 3 phase, 115/200 volt, 400 hz. generator set. series 500062
Table of Contents

Advertisement

OM-2226 / Operation and Maintenance Manual
60CU20 / Series 500062 / 400 Hz. Generator Set
1. Exciter Core Flange
2. Exciter Core Lamination
The exciter armature is mounted on the rear portion of the main generator armature shaft, which extends
rearward beyond the rear generator bearing into the exciter housing (See Figure 1). Because of its
location on the shaft, the exciter armature must be removed for rear main bearing replacement. The
exciter armature has two M10-1.5 tapped holes in its diode mounting plate to accommodate pulling it off
the shaft.
Since the removal and installation of exciter armatures can be rather complicated, this manual has been
prepared to assist mechanics in the operation. It may be necessary to remove the exciter armature
several times for bearing replacement during the life of a generator set.

2) Exciter Armature

The exciter armature used in this generator set consists of a revolving winding assembly on a laminated
core, a rectifier assembly (diode mounting plate with diodes), and a mounting flange. The flange, core,
and diode mounting plate are bolted together to make the complete exciter armature.
May 2, 2013
3. Diode Mounting Plate
4. Silicon Diode
Exciter Armature
Figure 2
Chapter 3-1
Page 2