d) DC Output Specifications (with optional TR unit)
Output Power Rating
Output Voltage
Load Capacity (Continuous)
Current Limiting Capability
Peak/Starting Load Capacity
Output cable size
e) DC Protective System Specifications
Condition
Over Voltage
Output Overload
f)
Engine Specifications
Manufacturer and Model
Type
Bore and Stroke
Displacement
Horsepower
Idle speed
Normal governed speed
Firing Order
Electrical system
Lubricating oil capacity (w/ filter)
Coolant capacity system
g) Normal Operating Characteristics
Engine oil pressure (warm and at rated speed 2000 RPM)
Engine coolant temperature (normal operation)
May 2, 2013
17.1 kW
28.5 VDC
600 A
100 to 2500 A
2000 A for 10 seconds
4/0
Trip Point
Time Delay
32-34 VDC
2 seconds
2700 A
2 seconds
2000 A
10 seconds
1500 A
30 seconds
1200 A
90 seconds
750 A
600 seconds
Cummins Engine Company / QSB4.5
4 cylinder, 4 cycle diesel, electronic controlled
4.21 in. x 4.88 in. (107 mm x 124 mm)
3
275 in
(4.5 L)
109 hp (81 kW)
1000 ± 50 rpm
2000 rpm
1-3-4-2
12 VDC
11.6 quarts (11 liters)
20 quarts (18.9 liters)
45 to 90 PSI (445 to 621 kPa).
160 to 200º F (71 to 93º C).