SiENBE04-925_A
Troubleshooting
∗ An output overcurrent signal may result from wrong internal wiring. If the wires have been
Check No.07
Refer to P.121
Check No.08
Refer to P.121
Check No.13
Refer to P.123
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
disconnected and reconnected and the system is interrupted by an output overcurrent, take the
following procedure.
Check No. 07
Check the installation condition.
Stop valve fully open?
YES
Turn off the power and turn it on
again to start the system. See if the
same error occurs.
Error again?
YES
Turn off the power and disconnect
the harnesses U, V, and W.
Check with the inverter checker (∗).
Any LED off?
NO
Check No. 13
Check the power module.
Normal?
YES
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check the supply voltage.
Voltage as
rated?
YES
Short circuit
or wire breakage
between compressor's coil
phases?
NO
Check No. 08
Check the discharge pressure.
NO
NO
Monitor the supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
∗ Instantaneous supply voltage
drop
∗ Compressor overloaded
∗ Short circuit
∗ Inverter checker
Part No.: 1225477
YES
NO
NO
YES
Troubleshooting
Fully open the stop valve.
Keep on using as it is.
Check the connectors and
other components.
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
Replace the PM1.
(Replace the outdoor unit
PCB.)
Correct the power supply.
Replace the compressor.
(R12016)