Chase Ventilation – Side Configuration
If ventilation is provided from the side, you must leave a 2" air gap to the both sides of the fireplace
(see illustration below). The ventilation air passes from the grills, through the chase, into the side
vents and exits through the convection air outlet.
Max.. 5-1/2"
When ventilating from the sides, you must use both small grills (16-1/4" x 4" outside dim.), or
equivalent free air opening (see note above). One grill must be placed on each side of the fireplace.
Vertically, the grills must be placed within 24" of the base of the fireplace (see illustration below).
If placed on a side wall, the grills must be placed directly to the side of the fireplace.
If placed on the front wall, the grills must be placed within 12" of the fireplace.
© Travis Industries
Installation
(for qualified installers only)
This shaded area on both sides of the fireplace must be left
unobstructed when using the side chase ventilation configuration.
MIn. 2"
TOP OF FIREPLACE
8/24/2017 - 1450
17
42 Apex CF