Minimum Vent Configuration

 Use 5x8" Diameter Coaxial Vent
 NOTE: Use the included thimble assembly whenever passing through a wall. (use on front
and back of wall penetration). See picture below.
 The termination must fall within the shaded area shown in the chart. Use the indicated
restrictor positions.
 One 45° elbow may be used on the horizontal run.
 HINT: Use minimum vent kit "H" (96200332) from Travis Industries (additional vent may be
required).
5 feet (1.5 m)
0 feet
Use the included wall thimble when
penetrating a wall. Part #96200101
© Travis Industries
Installation
(for qualified installers only)
Exhaust Restrictor # 1 (stock)
Diffuser Closed (stock)
8" Vent
2' Vertical Section Attached Directly to Fireplace
Max. 4' Horizontal Section(s)
Min. 3.9" Horizontal Section
1/2/19 - 1458
29
PB 72 MV/GSB2 Install