Omron CJ1W-PNT21 Operation Manual page 84

Profinet io controller unit
Hide thumbs Also See for CJ1W-PNT21:
Table of Contents

Advertisement

Allocated CIO Area Words
Bit
Name
00
All IO Devices are in
Data Exchange
01
All IO Devices have
consumed output
data.
02
At least one IO
Device has
consumed output
data
03
Reserved
04
IO Device Alarm
received
05~15
Reserved
5-2-6
IO Device Input Valid flags (Word n+9 ~ Word n+16)
70
15 14 13 12 11 10 9
Word n+7
/i
Status
If all Active IO Devices allocated to the CJ1W-PNT21 provide valid input
data, this flag will be ON. If one of the IO Devices does not provide data or its
data is marked as invalid, this flag will be OFF.
OFF
ON
If all IO Devices allocated to the CJ1W-PNT21 have processed the sent
output data, this flag will be ON. If one of the IO Devices does not process
output data this bit will be OFF.
OFF
ON
If at least one of the IO Devices allocated to this IOC has processed the sent
output data this flag will be ON. If none of the IO Devices has processed the
sent output data this flag will be OFF.
OFF
ON
---
If an IO Device Alarm has been received by the IO Controller this flag will be
ON. It will be OFF if all alarms have been read or cleared.
OFF
ON
---
The IO Device Data Exchange Active flags indicate for each IO device if it is in
Data Exchange mode with the PROFINET IO Controller Unit. The flags are
allocated to a block of eight CIO words, and each bit in the block corresponds
to a IO Device number as set in the DTM (IO Device Setup tab).
8
7
6
5
4
3
2
1
Figure 5.7: Word n+7
Unit operation
CJ1W-PNT21 does not receive data from one or
more IO Devices
CJ1W-PNT21 receives invalid input data from
one or more IO Devices
CJ1W-PNT21 receiving valid data from all IO
Devices.
One or more IO Devices have not processed the
sent output data.
All IO Devices have processed the sent output data.
None of the IO Devices have processed the sent
output data
At least one of the IO Devices has processed the
sent output data.
This bit will be set to OFF by the Unit.
No new IO Device Alarms have been received.
One or more new IO Device Alarms have been
received.
This bit will be set to OFF by the Unit.
Section 5-2
0
All IO Devices in
Data_Exchange
All IO Devices have
consumed output data
At least one IO Device has
consumed output data
IO Devices Alarm received