Omron CJ1W-PNT21 Operation Manual page 18

Profinet io controller unit
Hide thumbs Also See for CJ1W-PNT21:
Table of Contents

Advertisement

CJ1W-PNT21 PROFINET IO Controller Unit
2-2-2
Specifications
Functional specifications
Item
Installation
Environment
Front case
4
Various status and error flags indicating the status of the Unit and the
PROFINET IO network.
An error log for recording error history data.
/i
Model
Applicable PLC series
Unit classification
Mounting position
Number of Units that can be
mounted
Applicable unit numbers
Current consumption
Dimensions (WxHxD)
Weight
Ambient operating temperature
Ambient operating humidity
Storage temperature
Vibration resistance
Shock resistance
Dielectric strength
Conformance to EMC and
Electrical safety standards
Settings
Indicators
PROFINET IO Connector
Specification
CJ1W-PNT21
CJ-series
CJ-series CPU Bus Unit
CPU Rack or Expansion Rack
16 (restrictions may apply for certain PLC types)
0 to F (hex)
420mA at 5V DC from the PLC power supply.
31 x 90 x 65 mm
100 gram (typical)
0 °C to +55 °C (no icing or condensation)
20% to 90% Relative Humidity with no condensation
−20 °C to +75 °C (no icing or condensation)
Conforms to IEC60068-2-6, test Fc 10 to 58.4Hz, 0.25mm-
amplitude, 54.8 to 300Hz, acceleration: 29.4m/s2 in X, Y
and Z directions for 120 minutes each. (Total time: 12 linear/
sweeps * 10 minutes / sweep = 120 minutes)
Conforms to IEC60068-2-27, test Ea.196m/s2 three times
each in X, Y, and Z directions.
600 VAC (between isolated circuits)
EN6100-6-1: 2001
EN61000-6-4: 2001/CISPR11
EN 61131-2: 1994+a12:2000
Unit Number rotary switch, range:0~F (hex)
Two rotary switches (reserved)
LEDs indicating Unit status and PROFINET status;
Two-digit, 7-segment display
Module Status, MS (Green/Red LED)
Network Status, NS (Green/Red LED)
Data Exchange Status, 100M (Yellow LED)
Network Activity, COMM (Yellow LED)
1 x RJ45 8-pin Modular Connector
(conforming to ISO 8877)
Section 2-2

Advertisement

Table of Contents
loading

Table of Contents