Omron CJ1W-PNT21 Operation Manual page 105

Profinet io controller unit
Hide thumbs Also See for CJ1W-PNT21:
Table of Contents

Advertisement

Configuring the IO Devices
Adding/Inserting Modules
Note
The selected modules for this device. Modules can be added through the
Add Module button.
Details of the selected module. It is separated in I/O data and Parameters.
If needed the Parameters are settable. Which ones is defined in the
GSDML file.
By pressing the Add Module button a Module is added to the end of the
Module list.
The correct Module is select by a dropdownlist.
The correct order of the modules is selected by the slot number. A list of
available slotnumbers is displayed. Select the correct slotnumber for the
module.
1 The selected I/O modules are sent to the IO Device, in the same
sequence as selected in the user interface. Depending on the device,
the sequence may be checked by the IO Device. If an incorrect
sequence is sent, the I/O configuration is rejected. This is for exam-
ple the case with the OMRON GRT1-PNT PROFINET IO Device
2 A mandatory I/O module sequence is sometimes indicated in the
GSDML file, by using non-PROFINET standard GSDML file key-
words (i.e. only interpreted by a specific configurator). The Generic
IO Device DTM does not check such keywords. In this case, refer to
the manual of the specific device for details.
3 Also in this window are the maximum values, which can be set, and
the totals of I/O data that actually have been set. If - while selecting
I/O modules - one of the maximum values is exceeded, a warning
message will be displayed.
When done, making the I/O configuration settings, press the Apply button at
the bottom of the window. Next, select the Parameters, to make the necessary
parameter selections.
Figure 7.7: Add module
Section 7-3
91

Advertisement

Table of Contents
loading

Table of Contents