CJ1W-PNT21 PROFINET IO Controller DTM
Note
4-3-3
Configuration
Control
Set Device Name
Reset to factory
defaults.
1 It is required for the PC to have an Ethernet connection to the Network to perform
these operations.
2 Be sure to set the Device Name of the IO Device to exactly the same value as set
in the IO Controller's IO Device setup sub-item.
Find field
In the Find field a selection of the found IO devices can be made. The search
string can be used with wildcard characters (like *). The search is done on all
fields of the Device Online list.
The Main item "Configuration" (see figure below) provides the following four
sub-items:
PLC Setup
IO Controller Setup
IO Device Setup
IO Device Area
Figure 4.8: PROFINET IO Controller Configuration
Each sub-item is described in the sections below.
Description
The Device Name is used by the IO Controller to recognize
the IO Device on the network, to download parameters to the
IO Device and initiate I/O Data communication. Setting the
Device Name is mandatory.
According to the PROFINET specification the name may only
contain lower case characters, dashes and numbers. During
entry of the Device Name the characters entered are
checked and corrected for possible illegal characters.
The selected IO Device is reset to factory default settings.
This normally means no Name and no IP Address (0.0.0.0)
Section 4-3