Step 1: Set The Reference In Far End Source Mode - Fluke Versiv User Manual

Cabling certification product family
Hide thumbs Also See for Versiv:
Table of Contents

Advertisement

Versiv Cabling Certification Product Family
Users Manual

Step 1: Set the Reference in Far End Source Mode

Turn on the tester and source let them sit for a minimum of
1-1
5 minutes. Let them sit longer if they are above or below
ambient temperature, or if the instructions for the source
specify a longer time.
Make sure that the home screen shows the correct settings for
1-2
the job, and the test type is Far End Source.
To make sure that other settings are correct, tap the test
setup panel, make sure the correct test is selected on the
CHANGE TEST screen, then tap EDIT to see more settings.
Table 6 on page 111 describes the settings.
Clean and inspect the connectors on the tester, source, and test
1-3
reference cords.
On the home screen tap SET REF.
1-4
In the TEST MODE window, select Auto CertiFiber Pro or the
1-5
type of source you will use, then tap DONE.
On the SET REFERENCE screen, tap RUN WIZARD.
1-6
To only set the reference, and not measure the
loss of your test reference cord, tap SKIP WIZARD
on the SET REFERENCE screen.
Fluke Networks recommends that you measure
the loss of your test reference cord each time you
set the reference.
Make the connections to set the reference as shown on the
1-7
screen, then tap NEXT to see the completed connections.
Figure 53 also shows the completed connections.
The SET REFERENCE screen shows reference
connections for the selected reference method.
Figure 53 shows connections for the 1 Jumper
reference.
136
Notes
Note

Advertisement

Table of Contents
loading

Table of Contents