P214
4 mA Output Trim
Trims the 4 mA output level for the output selected, outputs 1 to 3 (P214 - 01 to – 03)
trim adjust the output to agree with a milliameter or other external mA input device.
Scroll the trim value up or down
P215
20 mA Output Trim
Trims the 20 mA output level for the output selected, outputs 1 to 3 (P215 - 01 to - 03)
trim adjust the output to agree with a milliammeter or other external mA input device.
Scroll the trim value up or down
P220
mA Output Damping
Sets the damping for the output selected, outputs 1 to 3 (P220 - 01 to - 03)
the speed at which the mA output reacts to change. The greater the damping value, the
slower the response. If the value is 0, the mA output assumes the damping set in P080
f
(
= 0.00).
Enter the damping value, range 0.001 – 999
P250
mA input range
Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to - 02).
Entry:
1 = 0 - 20 mA
f
2 = 4 - 20 mA
P255
mA Input Function
Assigns the mA input function for the input selected, inputs 1 to 2 (P250 - 01 to - 02)
Entry:
f
0 = OFF
1 = PID setpoint
2 = PID process variable
3 = Online calibration
4 = Moisture compensation
5 = Incline compensation
1)
BW500/L has one output, parameters will not present multiple indexes.
2)
Not available with BW500/L.
3)
Valid only if Online Calibration is turned on, (P355 = 1).
7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS
2)
2)
3)
1)
. The
1)
. The
1)
. Damping sets