Siemens Milltronics BW500 Operating Lnstructions page 126

Hide thumbs Also See for Milltronics BW500:
Table of Contents

Advertisement

P200
mA Output Range
Sets the mA range for the output selected, outputs 1 to 3 (P200 - 01 to - 03)
Entry:
1 = 0 - 20 mA
f
2 = 4 - 20 mA
P201
mA Output Function
Assigns the mA output function for the output selected, outputs 1 to 3 (P201 - 01 to - 03)
Entry:
f
1 = rate
2 = load
3 = speed
4 = PID control output
P204
mA Output Average
Sets the averaging period, in seconds, for the rate output for output 1 only.
The instantaneous mA values are averaged for the set period, and then the average value
is output during the next period while a new average is being calculated.
Entry:
f
0 = OFF
1 – 999 = averaging period
P212
mA Output Minimum
Sets the minimum mA limit for the output selected, outputs 1 to 3 (P212 - 01 to - 03)
limit sets the lower mA range (0 or 4 mA) to a minimum output value (
Enter limit value, range 0 - 22
P213
mA Output Maximum
Sets the maximum mA limit for the output selected, outputs 1 to 3 (P213 - 01 to - 03)
limit sets the upper mA range (20 mA) to a maximum output value (
Enter limit value, range 0 - 22
1)
BW500/L has one output, parameters will not present multiple indexes.
2)
Not available with BW500/L.
3)
Valid for outputs 2 and 3, only if PID system (P400) is enabled.
Page 120
Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS
2) 3)
1)
.
1)
1)
. The
f
= 3.80).
1)
. The
f
= 22.00).
7ML19985DK05