Operating Guide ECL Comfort 210/296/310, application A232 / A332

5.8 Application

The section "Application" describes specific application related
issues.
Some of the parameter descriptions are universal for different
application keys.
The subtypes A232.1, A332.1 and A332.2 use the input S7 to stop
the circulation pump.
The subtypes A232.1, A332.1, A332.2 and A332.4 use the input S8
to make override to Comfort or Saving.
The subtype A332.4 use the input S7 to make override to Heating.
The subtype A332.4 use the input S9 to make override to Cooling.
The value "Accumulated temperature" is a filtered (dampened)
value for room and outdoor temperatures. It is used to express the
heat stored in the walls of the house.
The accumulated temperature values can be read in: MENU >
Common controller > Input overview
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Application
ECA addr. (ECA address, choice of Remote Control Unit)
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
See Appendix "Parameter ID overview"
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
MENU > Settings > Application
P exercise (pump exercise)
Exercises the pump to avoid blocking in periods without heat demand.
See Appendix "Parameter ID overview"
OFF:
The pump exercise is not active.
ON:
The pump is switched ON for 1 minute every third day at
noon (12:14 hours).