MENU > Settings > Application
Activation, acc. T (Activation of cooling mode, based on
accumulated outdoor temperature value)
The controller activates cooling when the accumulated outdoor
temperature value exceeds the set value by 0.5 degrees. The controller
deactivates cooling when the accumulated outdoor temperature value falls
0.5 degrees below the set value.
The accumulated outdoor temperature value is shown in 'Input overview'
(see 'Common controller'). The filtering for accumulated outdoor
temperature value can be set in parameter 'Filt. acc. outd. T' (ID 1x154).
See Appendix "Parameter ID overview"
Value: Set the activation value
MENU > Settings > Application
Filt. acc. room T (Filter for accumulated room temperature
value)
The measured room temperature is filtered (dampened) by means of the
filtering constant.
The filtered (accumulated) room temperature value is used for the cut-in
and cut-out of cooling.
The accumulated room temperature value is shown in 'Input overview' (see
'Common controller').
See Appendix "Parameter ID overview"
Low value:
Low filtering (minor dampening)
High value:
High filtering (major dampening)
Value
Set the filtering value
VI.JM.G2.02
Example: Switching ON the cooling mode:
1x144
=
X
Time
=
T
Temperature
# 1 # =
Accumulated outdoor temperature
# 2 # =
Activation, acc. T (ID12144)
Example, filtering:
1x153
=
X
Time
=
T
Temperature
# 1 # =
Actual room temperature
# 2 # =
Filtered room temperature value (low filtering)
# 3 # =
Filtered room temperature value (high filtering)