Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Application
M exercise (valve exercise)
Exercises the valve to avoid blocking in periods without heat demand.
See Appendix "Parameter ID overview"
OFF:
The valve exercise is not active.
ON:
The valve opens for 7 minutes and closes for 7 minutes
every third day at noon (12:00 hours).
MENU > Settings > Application
P post-run
Heating applications:
The circulation pump in the heating circuit can be ON for a number of
minutes (m) after heating stop. Heating stop is when the desired flow
temperature gets lower than the setting in 'P heat T' (ID no. 1x078).
Cooling applications:
The circulation pump in the cooling circuit can be ON for a number of
minutes (m) after cooling stop. Cooling stop is when the desired flow
temperature gets higher than the setting in 'P cool T' (ID no. 1x070).
This P post-run function can utilize the remaining energy in for example a
heat exchanger.
See Appendix "Parameter ID overview"
0:
The circulation pump stops immediately after heating
or cooling stop.
Value: The circulation pump is ON for the set time after heating
or cooling stop.
MENU > Settings > Application
P cool T (cooling demand)
When the desired flow temperature is below the set temperature in 'P cool T' ,
the controller automatically switches ON the circulation pump.
See Appendix "Parameter ID overview"
Value: The circulation pump is switched ON when the desired
flow temperature is below the set value.
MENU > Settings > Application
Circ. P frost T
Set the outdoor temperature value at which the DHW circulation pump is to
be active to protect the DHW circuit against frost.
See Appendix "Parameter ID overview"
OFF:
The DHW circulation pump is not active.
Value:
The DHW circulation pump is active when the outdoor
temperature is lower than the set value.
100 | © Danfoss | 2017.08
1x023
1x040
1x070
The valve is fully closed as long as the pump is not switched on.
1x076
VI.JM.G2.02