Danfoss ECL Comfort 210 Operating Manual page 106

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Application
Filt. acc. outd. T (Filter for accumulated outdoor
temperature value)
The measured outdoor temperature is filtered (dampened) by means of
the filtering constant.
The filtered (accumulated) outdoor temperature value is used for the cut-in
and cut-out of cooling.
The accumulated outdoor temperature value is shown in 'Input overview'
(see 'Common controller').
See Appendix "Parameter ID overview"
Low value:
Low filtering (minor dampening)
High value:
High filtering (major dampening)
Value
Set the filtering value
MENU > Settings > Application
Act., acc. room T (Activation of cooling mode, based on
accumulated room temperature value)
The controller activates cooling when the accumulated room temperature
value exceeds the set value by 0.5 degrees. The controller deactivates
cooling when the accumulated room temperature value falls 0.5 degrees
below the set value.
The accumulated room temperature value is shown in 'Input overview' (see
'Common controller'). The filtering for accumulated room temperature
value can be set in parameter 'Filt. acc. room T' (ID 1x153).
See Appendix "Parameter ID overview"
Value: Set the activation value
106 | © Danfoss | 2017.08
Example, filtering:
1x154
=
X
Time
=
T
Temperature
# 1 # =
Actual outdoor temperature
# 2 # =
Filtered outdoor temperature value (low filtering)
# 3 # =
Filtered outdoor temperature value (high filtering)
Example: Switching ON the cooling mode:
1x156
=
X
Time
=
T
Temperature
# 1 # =
Accumulated room temperature
# 2 # =
Act., acc. room T (ID 12156)
VI.JM.G2.02