Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Return limit
Limit (return temp. limitation)
Set the return temperature value you accept for the system.
See Appendix "Parameter ID overview"
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.' .
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Set the outdoor temperature value for the low return temperature limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1' .
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1' .
MENU > Settings > Return limit
Low T out X2 (return temp. limitation, low limit, X-axis)
Set the outdoor temperature value for the high return temperature
limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2' .
80 | © Danfoss | 2017.08
Subtype A332.3 only:
Temperature sensors S5 (heating circuit) and S6 (cooling circuit) can be
used for either return temperature limitation or surface temperature
limitation.
Functionality selection is done by setting an influence factor.
If influence factors are set for both Return and Surface limitation, there
will not be any limitation.