Danfoss ECL Comfort 210 Operating Manual page 45

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332
Navigation, A232, application A232.1, cooling
Home
MENU
Schedule
Settings
Holiday
Alarm
Influence overview
VI.JM.G2.02
Sub-menu
Flow temperature
Room limit
Surface limit
Application
Temp. monitor.
Alarm overview
Des. flow T
A232
ID no.
Function
Schedule
Cool curve
12178
Temp. max.
12177
Temp. min.
12164
Dew p. T offset
12182
Infl. - max.
12183
Infl. - min.
12015
Adapt. time
12157
Room T influence
12027
Room T diff.
12060
Limit
12063
Infl. – min.
12061
Adapt. time
12144
Activation, acc. T
11179
Summer, cut-out
12500
Send desired T
12092
Standby T
12141
Ext. input
12142
Ext. mode
Selectable
12147
Upper difference
12148
Lower difference
12149
Delay
12150
Lowest temp.
Clear alarm
Max. temp.
Temp. monitor.
T sensor defect
Room lim.
Surface limit
Holiday
SCADA offset
Ext. stop cmd
A232.1
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
© Danfoss | 2017.08 | 45