Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Optimization
Boost
Shortens the heating-up period by increasing the desired flow temperature
by the percentage you set.
See Appendix "Parameter ID overview"
OFF:
The boost function is not active.
Value: The desired flow temperature is increased temporarily
with the set percentage.
In order to shorten the heating-up period after a saving
temperature period, the desired flow temperature can be increased
temporarily (max. 1 hour). At optimizing the boost is active in the
optimization period ('Optimizer').
If a room temperature sensor or an ECA 30 / 31 is connected, the
boost stops when the room temperature is reached.