Danfoss ECL Comfort 210 Operating Manual page 107

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A232 / A332
MENU > Settings > Application
Summer, cut-out (limit for heating cut-out)
See Appendix "Parameter ID overview"
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
MENU > Settings > Application
T out depend. (Outdoor temperature dependent
activation of cooling mode)
The application can do the change-over between heating and cooling
based on:
room temperature only
or
room and outdoor temperatures
See Appendix "Parameter ID overview"
No:
Change-over is related to room temperature only.
Yes:
Change-over is related to room temperature and
outdoor temperature.
Select the desired functionality.
VI.JM.G2.02
Summer, cut-out
1x179
= Time
X
= Temperature
Y
= Actual outdoor temperature
# 1#
# 2 # = Cut-out temperature (1x179)
# 3 # = Accummulated (filtered) outdoor temperature
# 4 # = Heating enabled
# 5 # = Heating disabled
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
1x498
© Danfoss | 2017.08 | 107

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 296A232Ecl comfort 310A332

Table of Contents